Yoohoon.cn
+ --------------------------- +
DCWell intelligent liquid-cooled analog load device-Blind plug in complete cabinet-Single cabinet modular 120KW load-YH-SC15
+ -------------------------- +
DCWell Intelligent Liquid Cooling Analog Load Device - Blind Plug Whole Cabinet - Single Cabinet Modular 120KW Load-YH-SC15
描述
DCWELL Liquid Cooling Dummy Load YH-SC15
parameter configuration tablesystem parametersDescription
Load grading DC48V1kW,1kW,1kW,2kW,2kW,2kW,2kW,2kwThe heating resistor is made of PTC material and is a constant power resistor
main circuit connectionblind insertionModel CB-01-00-7399
loading modelocal display screenDisplay screen is equipped with gear button
Water circuit interfaceblind insertionThe model is UQDB/A/204-Z01A1JE-
water flow21L/minEquipped with electric regulating valve, installed with water inlet, adjustable flow resistance from 30Kpa to 100Kpa
Overload protectionThe main load circuit is equipped with fusesOverload and short circuit protection, display triggers alarm
over-temperature protectionMonitor the water temperature at the inlet and outlet of the load belt. When the water temperature is too high, the alarm is pressed to stop and cut off the load.Threshold value 75C, inlet and outlet water can be set according to demand
pressure protectionNegative I can monitor the inlet and outlet water pressure. When the pressure exceeds the set value, an alarm will be pressed to stop and cut off.LoadInlet and outlet water can be set according to needs
Chassis sizeW 440mm* H 177mm*D 900mmVolume:4U
Contact us